Energy Consumption Meter DLPMC-24

DIN-rail installation, real-time analysis and harmonics up to the 10th order.

01 · Status at a glance

The front LEDs show power, SIM and 4G coverage at a glance, without opening the panel.

02 · Measurement connections

R, S, T and N terminals for voltage and power supply, three current-clamp inputs, Ethernet as backup and USB-C for expansions such as earth-leakage monitoring.

03 · Data over 4G

Sends data to the Delphos platform over 4G LTE-M with a built-in SIM: just screw on the antenna.

Overview

Measures the electricity consumption and generation of a single-phase or three-phase line: voltage, current, power, power factor, active and reactive energy, frequency and harmonics up to the 10th order, per phase.

  • It is installed in the main electrical panel or in sub-panels, is powered from the very line it measures and sends the data to the Delphos platform over 4G LTE-M, with Ethernet as backup.
  • It is designed for analysing and managing consumption; it is not a billing meter.

Features

Built for the everyday reality of your site.

  • DIN-rail installation (4 modules), powered from the very line it measures: no external power supply.

  • Per phase: voltage, current, active, reactive and apparent power, power factor, energy, frequency and harmonics up to the 10th order.

  • Measures consumption and generation (for example, photovoltaic); the platform adds up each meter according to its type and its position in the installation.

  • 100 A, 200 A or 400 A clamps, or flexible Rogowski coil up to 1000 A.

  • 4G LTE-M with built-in SIM as the main connection and Ethernet as backup.

  • It only sends data: it does not accept commands or incoming connections.

With or without an IP66 enclosure.

The same electronics, inside the electrical panel or mounted in an IP66 metal enclosure next to it.

Energy Consumption Meter DLPMC-24 — Without IP66 caseEnergy Consumption Meter DLPMC-24 — With IP66 case

Specifications

Technical specifications

Connectivity
  • 4G LTE-M (main)
  • Ethernet (backup)
  • API
Ports
  • Power supply and voltage measurement: terminals R, S, T, N and PE
  • 3 current clamp inputs (3.5 mm jack)
  • Ethernet RJ-45 (4G backup)
  • 4G antenna (female SMA connector) and built-in SIM
Power supply100–400 V~ between phase and neutral, 50/60 Hz, taken from the line itself (between T and N; the neutral is mandatory). Maximum consumption: 6 W.
Mounting35 mm DIN rail (4 modules), in the main electrical panel or in sub-panels, never at the service entrance, or in an IP66 metal enclosure next to the panel. Indoor, from 5 to 40 °C. Measurement category III, 300 V.
Supported sensors
  • Current clamps DLPPZ-17 (100 A), DLPPZ-24 (200 A) and DLPPZA-36 (400 A)
  • Flexible Rogowski coil (1000 A)
OptionsIn the electrical panel (DIN rail) or fitted in an IP66 metal enclosure, for the same price

3D model

Turn it and see it from every side

Energy Consumption Meter DLPMC-24

Drag to rotate it; scroll or pinch to zoom in.

Delphos platform